Please use this identifier to cite or link to this item: http://hdl.handle.net/10603/11543
Title: Performance analysis of centrifugal atomizer type air cooler suitable for industrial sheds located in tropical climates
Researcher: Senthilkumar K
Guide(s): Srinivasan, PSS
Keywords: Performance analysis, centrifugal atomizer, air cooler, industrial sheds, tropical climates
Upload Date: 27-Sep-2013
University: Anna University
Completed Date: 
Abstract: In a tropical country like India, industrial sheds are constructed with masonry walls and asbestos cement sheet roofs, which have higher cooling load. Air conditioning such sheds using conventional Mechanical Vapour Compression type air conditioning systems are practically difficult and hence not practiced. Evaporative cooling will be a suitable alternative. In this context, the present research work aims to develop a centrifugal atomizer type evaporative air cooler suitable for large industrial sheds located in tropical climates and to carry out performance improvements. An experimental facility has been developed which has a centrifugal humidifier type evaporator capable of cooling an industrial shed of 10 m × 3 m floor area having an asbestos cement sheet roof. Using the facility, effect of spinning disc diameter, its speed, breaker strip geometry, length of evaporation chamber, air flow rate and supply water flow rate are tested. Experiments are carried out from 6.00 AM to 6.00 PM during May 2009, and data from 7.00 AM to 5.00 PM are used for calculations. Then using Taguchi method, optimization of parameter settings has been carried out. The research work has shown that the centrifugal atomizer type evaporator is capable of cooling large air volumes and is suitable for cooling large industrial sheds. The drops in average interior DBT when compared to the corresponding outside DBT over a day obtained are 8-12 ºC. Rectangular shaped breaker strips are found to provide higher performance, when compared to triangular and circular ones. Increase in disc diameter, disc speed and evaporation chamber length increases the humidification efficiency. The optimization study has shown that disc speed, air flow rate and supply water flow rate influence the system performance by 33 %, 21 % and 19 % respectively, whereas the influences of other parameters are less than 5 %. With optimized settings, about 32 % higher performance is obtained when compared to the initial parameter setting. newline newline newline
Pagination: xix, 128
URI: http://hdl.handle.net/10603/11543
Appears in Departments:Faculty of Mechanical Engineering

Files in This Item:
File Description SizeFormat 
01_title.pdfAttached File49.44 kBAdobe PDFView/Open
02_certificates.pdf760.35 kBAdobe PDFView/Open
03_abstract.pdf14.21 kBAdobe PDFView/Open
04_acknowledgement.pdf14.75 kBAdobe PDFView/Open
05_contents.pdf51.41 kBAdobe PDFView/Open
06_chapter 1.pdf189.35 kBAdobe PDFView/Open
07_chapter 2.pdf63.62 kBAdobe PDFView/Open
08_chapter 3.pdf3.78 MBAdobe PDFView/Open
09_chapter 4.pdf356.11 kBAdobe PDFView/Open
10_chapter 5.pdf60.73 kBAdobe PDFView/Open
11_chapter 6.pdf18.19 kBAdobe PDFView/Open
12_appendices 1 to 3.pdf258.95 kBAdobe PDFView/Open
13_references.pdf36.24 kBAdobe PDFView/Open
14_publications.pdf13.99 kBAdobe PDFView/Open
15_vitae.pdf12.19 kBAdobe PDFView/Open
Show full item record


Items in Shodhganga are licensed under Creative Commons Licence Attribution-NonCommercial-ShareAlike 4.0 International (CC BY-NC-SA 4.0).

Altmetric Badge: